Roof Louvre Blade - Commercial (RLB-C)

Product features and details.
1
Product Overview

Roof Louvre Blade – Commercial (RLB-C), are smoke vent and air supply units used in natural smoke and heat exhaust ventilation systems (nSHEVS). Mounted on roofs, louvre smoke vents exhaust smoke and heat from a building, allowing low level escape routes to be kept clear of smoke. Roof Louvre Blade – Commercial (RLB-C) units are fully certified to BS EN 12101-2. They are particularly suited to industrial and commercial buildings and may also provide natural comfort ventilation.


They are available in a wide range of sizes, louvre options and types of upstands. With the addition of polycarbonate glazing they can also bring natural daylight into the building. They may be installed at any angle, but are generally installed horizontally and supplied with aerodynamic wind shields as standard. They consume minimal energy during the opening and closing cycle and have high resistance to weather and are therefore suited for use on exposed and high wind areas. They provide good security, are impact resistant and do not create a fall hazard when open.

2
Specific Features

Fully certified to BS EN12101-2

Available in a wide range of sizes and options from 800 x 500mm to 2500 x 3800mm

Impact resistant to EN 1873 1200 Joules

Available with polycarbonate glazing or solid insulated blades

Opening to 90° within 60 seconds

Consume minimal energy during operation

High resistance to weather and wind load

When open they are not a fall hazard

Thermal Transmission

Typical U-Values (W/m2.K)

Aluminium Insulated Blades: 1.75

Polycarbonate Blades: 1.77

Adaptor Base - Insulated: 1.38

Adaptor Base - Uninsulated: 5.80

Technical Data

Water tightness to EN 1873: Pass

Impact resistance to ACRM: Class B

Voltage: 24V DC

Opening Angle: 90°

Ambient Operating Temperature: -25°C / +70°C

Speed: 3.4mm/sec

Protection Degree: IP40

Force: 900N

Certification EN12101-2

Downward Load: 250N

Upward Load: 1500N

Resistance to Heat: B 300

Low Ambient Temperature: -25°C

Reliability: 300

Impact Resistance: Class B

Fire Rating: AA

Water Tightness: Pass

Certification ACR(M) 2011

Impact Resistance: Class B

Certification BS 476 : Part 3

Fire Rating: AA

Certification EN 1873:2005

Water Tightness: Pass

For all information regarding this product please download its datasheet.

Installation Instructions

How to install the RLB-C, by the people who make it
Form builder's curb
Mount vent to curb
Complete connections
Get the installation guide.
Suited to natural systems
The RLB-C is usually found in natural systems at the head of shaft.
Related Products
Shaft Single Leaf - Residential (SSL-R)
View
Roof Single Leaf - Residential (RSL-R)
View
Firefighter's Vent Override Switch (CAS-R | FVOS)
View
Networked Controls System - Residential (CNS-R)
View