System type
Customisations available
Lead times
Dedicated Sertus delivery
Certified to BS EN 12101-2
Approved Document B & Part L compliant
Supplied with fixings for faster install
Wide range of sizes
Opens to 160° in under 60 seconds
Optional roof access feature
Opens to 160° within 60 seconds for fast smoke and heat extraction
Insulated solid lid with Rockwool insulation for high-performance smoke ventilation
Natural smoke ventilation, mechanical ventilation and roof access capability
Pre-wired 24 V DC actuator supplied for simple installation
Aluminium or PVC base frame options to suit project requirements
Integrated flashings (collar option) for weatherproofing
Modular linking option for larger openings
Optional fall arrest grid and end switches
Durable construction designed for long-term performance
Square or rectangular – standard and bespoke sizes
Standard roof opening range:
Min: 900 × 900 mm
Max: up to 1600 × 2500 mm (aluminium) / 1600 × 2300 mm (PVC)
Insulated solid lid - Rockwool insulation or multiwall
Base frame options:
Aluminium collar with Rockwool insulation
PVC base frame
Internal finish:
Aluminium: Powder-coated white aluminium
PVC: White PVC
External finish:
Powder-coated or mill finish aluminium (RAL colour customisable when using collar)
Certified to BS EN 12101-2
Compliant with BS EN 1873
Approved Document B & Part L compliant
Impact resistance: SB 1200 J
Air permeability:
Aluminium: Class 3 (BS 6375-1)
PVC: Class 2 (BS EN 1873)
Weather tightness: Pass
Wind load resistance: up to 1500 N
Snow load:
Aluminium: 250-2250 N
PVC: SL350–1000 N
Heat resistance: B300
Low temperature operation: -15 °C
Reliability: 10,000 + 1,000 cycles tested
Dual purpose ventilation
Opens to 160° within 60 seconds
Insulated solid lid (Rockwool or multiwall)
Aluminium (Rockwool insulated) or PVC
BS EN 12101-2 / EN 1873 compliant
SB 1200 J
Class 3 (Aluminium)
Class 2 (PVC)
Pass
Up to 1500 N
Up to 250–2250 N (Aluminium)
SL350–1000 N (PVC)
B300
-15 °C
Range: 1.10–1.25 W/(m²·K) (Aluminium)
1.37–2.68 W/(m²·K) (PVC)
Range: 0.50–2.48 m² (Aluminium)
0.20–1.50 m² (PVC)
Range: 0.70–3.90 m² (Aluminium)
0.39–2.89 m² (PVC)
Pre-wired 24 V DC
IP45
10,000 + 1,000 cycles
Roof-mounted assembly
Fully assembled, crane-lift ready
Insulated base flange (Aluminium), modular linking, end switches, fall arrest grid
Download a zip file containing all documents for this product.
Technical Data Sheet
Technical Data Sheet (U-Value Performance)
Installation Guide
Operation & Maintenance Manual
Declaration of Performance
Warranty
BIM Model
Yes. The Roof Single Leaf Vent | Solid is available with either a Rockwool-insulated aluminium collar (RSL) or a PVC base construction (RSL-R). The RSL offers enhanced thermal performance and A1-rated construction, while the RSL-R provides a cost-effective alternative for a wide range of smoke ventilation applications.
Yes. A bespoke wind deflector can be specified to increase the aerodynamic free area where required.
The Roof Single Leaf Vent | Solid features a fully insulated solid lid, providing robust smoke ventilation where natural daylight is not required.
Yes. An opening limiter can be fitted where required. However, restricting the opening below 140° may affect compliance with BS EN 12101-2.
Yes. The solid lid is insulated as standard to help improve thermal performance.
Yes. The actuator can be specified on either the left- or right-hand side to suit the project requirements.
The top of the roof vent upstand should be a minimum of 300mm above the finished roof surface.
Yes. The Roof Single Leaf Vent can be installed on roof pitches of up to 20°.
We do not recommend installing permanent ladders adjacent to roof vents, as they may reduce the aerodynamic free area and affect smoke ventilation performance.
Where roof vents are installed in areas with regular roof access or foot traffic, appropriate edge protection or fall protection measures should be considered in accordance with the project's safety strategy.
The Roof Single Leaf Vent is designed to be low maintenance. Routine maintenance typically consists of periodic inspections and cleaning using warm soapy water.
Routine servicing of the smoke control system, including control panels and call points, is typically carried out from within the building. Some maintenance tasks on the roof vent itself may require roof access.
Yes. If the actuator requires replacement, it can typically be accessed and replaced from the roof without entering the building.
Yes. Sertus Roof Single Leaf Vents are CE marked in accordance with BS EN 12101-2, the harmonised European standard for natural smoke and heat exhaust ventilators.
Yes. The Roof Single Leaf Vent is classified BRoof (T4) for external fire performance.
No. Natural smoke vents are designed to extract smoke and heat from a building and are tested to BS EN 12101-2. Unlike smoke control dampers, they are not intended to provide compartmentation and therefore do not require a fire resistance classification.
Explore real projects using our smoke ventilation products across both residential and commercial sectors.